Complete Solutions
Heat Recovery Systems
Industrial fired boilers
Land Service
Product & Systems
References & Media
|
|
MISSION™ OL
PATENT PENDING
________________________________________________________________________________________
General
- The perfect "stand-by boiler"
- Start-up in 8-10 minutes
- Two-drum cylindrical water tube boiler
- Standard preassembled modules
- Top fired compact design
- Membrane wall design
- Made of mild carbon steel with elevated temperature properties
- Integrated burner for Natural gas and Fuel Oil
- Refractory is reduced to a protective layer at the bottom of the furnace
- Designed according to new PED/EN regulations
Design data
| Heat capacity: |
8 - 38.8 MW |
| Steam capacity: |
12 - 60 t/h |
| Design pressure: |
up to 18 bar(g) |
| Steam temperature: |
from saturated up to
290 ºC |
| Efficiency (DIN 1942): |
83 - 95% |
Capacity, Fuel economy, Dimensions & Weight

|
|
| Steam capacity Oil-firing |
Height "K" (incl. retraction of burner lance) * |
Diameter "D" (incl. insulation) * |
Height "H"
* |
Width "B" |
Boiler dry weight |
Boiler operation weight |
kg/h |
mm |
mm |
mm |
mm |
ton |
ton |
12,500 |
8,100 |
2,670 |
5,760 |
4,100 |
18.7 |
25.4 |
16,000 |
8,200 |
3,070 |
5,760 |
4,450 |
23.2 |
32.1 |
20,000 |
9,100 |
3,220 |
6,110 |
4,700 |
26.5 |
36.7 |
25,000 |
9,900 |
3,320 |
6,960 |
4,900 |
29.9 |
41.1 |
30,000 |
10,200 |
3,570 |
7,160 |
5,250 |
34.6 |
47.8 |
35,000 |
10,050 |
3,870 |
7,010 |
5,650 |
39.7 |
55.1 |
40,000 |
10,650 |
3,870 |
7,410 |
5,750 |
41.9 |
57.8 |
45,000 |
10,650 |
4,270 |
7,360 |
6,250 |
48.4 |
67.7 |
55,000 |
10,900 |
4,520 |
7,410 |
6,600 |
56.0 |
78.0 |
* Dimension of boiler pending final design with regards to NOx requirements, addition of superheater
and/or economizer.
DATA SHEET series