General
- Vertical cylindrical boiler made of mild steel
- Standard preassembled boiler unit
- Integrated control panel
- Pin tube elements
- Top-mounted fittings
- Ready to install
- Designed for operation with a monobloc type pressure jet or rotary cup burner
Design data
| Thermal output: |
up to 31.5 MW |
| Steam capacity: |
8.0 - 45.0 t/h |
| Design pressure: |
up to 11 or 18 bar(g) |
Description
MISSION™ OM is a high performance medium capacity oil-fired auxiliary boiler with a capacity range from 8 to 45 t/h. MISSION™ OM is a vertical cylindrical boiler constructed from standard modules. The boiler is delivered as a pre-assembled unit, minimising installation and maintenance time.
The MISSION™ OM is easy to ventilate, and 100% visual inspection of membrane walls can be undertaken.
The steam generated is very dry as the smoke tubes pass through the furnace thus overheating the steam.
The hot-water boiler version of MISSION™ OM is the SUNROD™ CHS. |
|
| |
|
Capacity, Fuel economy, Dimensions & Weight
| Steam capacity |
Design pressure |
Thermal output at 100% MCR |
Height "H" |
Diameter "D" (incl. insulation) |
Height "H"
* |
Width "B" |
Boiler dry weight |
Boiler operation weight |
kg/h |
bar (g) |
kW |
mm |
mm |
mm |
mm |
ton |
ton |
8,000 |
11 |
5,600 |
6,600 |
2,470 |
3,670 |
2,820 |
13.0 |
19.0 |
12,500 |
11 |
8,800 |
6,720 |
2,920 |
4,260 |
3,270 |
18.0 |
26.0 |
16,000 |
11 |
11,200 |
7,400 |
3,120 |
4,460 |
3,470 |
20.0 |
28.0 |
20,000 |
11 |
14,000 |
7,450 |
3,520 |
4,860 |
3,870 |
25.0 |
35.0 |
* With KB rotary cup burner.

| Steam capacity |
Design pres- sure |
Thermal output at 100% MCR |
Height "H" |
Dia- meter "D" (incl. insula tion) |
Width "W1" Heating coil removal
|
Width "W2" Burner removal * |
Flue gas outlet con- nected |
Boiler dry weight
** |
Water volume |
kg/h |
bar (g) |
kW |
mm |
mm |
mm |
mm |
DN |
ton |
ton |
14,000 |
18 |
9.8 |
7,300 |
3,000 |
2,015 |
3,320 |
700 |
19.0 |
8.3 |
16,000 |
18 |
11.2 |
7,800 |
3,000 |
2,015 |
3,440 |
700 |
20.3 |
8.1 |
20,000 |
18 |
14.0 |
7,900 |
3,300 |
2,165 |
3,595 |
900 |
24.7 |
10.0 |
25,000 |
18 |
17.5 |
8,700 |
3,300 |
2,165 |
3,820 |
900 |
27.0 |
10.5 |
| 30,000 |
18 |
21.0 |
9,000 |
3,600 |
2,315 |
4,000 |
1,000 |
32.9 |
12.6 |
| 35,000 |
18 |
24.5 |
9,620 |
3,900 |
2,465 |
4,775 |
1,000 |
38.4 |
15.1 |
| 40,000 |
18 |
28.0 |
9,660 |
4,100 |
2,565 |
4,735 |
1,200 |
43.3 |
16.6 |
| 45,000 |
18 |
31.5 |
9,660 |
4,100 |
2,565 |
5,690 |
1,200 |
45.7 |
17.0 |
* With KBSA steam atomizing burner.
** Without burner and accessories.
Capacity 45,000 kg/h is with extended furnace.
DATA SHEET series
© Aalborg Industries 2001, rev.: 3.0, October 2005 (Design data are subject to change without prior notice).